EasyManuals Logo

Siemens SIMATIC S7-300 Module data User Manual

Siemens SIMATIC S7-300 Module data
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #141 background imageLoading...
Page #141 background image
Digital modules
3.28 Relay output module SM 322; DO 16 x Rel. AC 120/230 V; (6ES7322-1HH01-0AA0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
3-93
Diagnostic interrupt
When diagnostic interrupts are enabled, incoming error events (initial occurrence) and
outgoing error events (error is cleared) are reported by means of interrupt.
The CPU interrupts execution of the user program and processes diagnostic interrupt OB 82.
You can call SFC 51 or 59 in OB82 in the user program to view detailed diagnostic data
output by the module.
Diagnostics data remain consistent until the program exits OB 82. The module
acknowledges the diagnostic interrupt when the program exits OB82.
Load restrictions in horizontal mounting position
In horizontal mounting position, the module loads must be restricted so that two adjacent
inputs or outputs do not exceed their rated load.
Load restrictions in vertical mounting position
In vertical mounting position, the module loads must be restricted so that four adjacent inputs
or outputs do not exceed their rated load.
See also
Parameters of SM 322; DO 8 x DC 24 V/0.5 A (Page 3-77)
3.28 3.28 Relay output module SM 322; DO 16 x Rel. AC 120/230 V;
(6ES7322-1HH01-0AA0)
Order number
6ES7322-1HH01-0AA0
Properties
Properties of SM 322; DO 16 x Rel. AC 120/230 V:
16 outputs, electrically isolated in groups of 8
Rated load voltage 24 VDC to 120 VDC, 48 VAC to 230 VAC
Suitable for AC/DC solenoid valves, contactors, motor starters, FHP motors and signal
lamps.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)