Analog modules
6.8 Analog input module SM 331; AI 2 x 12 bit; (6ES7331-7KB02-0AB0)
S7-300 Automation System Module data
6-72 Manual, 08/2006, A5E00105505-04
6.8.3 Additional information to SM 331; AI 2 x 12 bit
Unused channels
You must short-circuit unused channels and connect them to M
ANA
. This optimizes
interference immunity of the analog input module. For unused channels, set the "disabled"
instruction at the "measuring method" parameter. This reduces the module's cycle time.
If not used, short-circuit the COMP input.
Certain inputs of the channel group configuration may remain unused. To enable diagnostic
functions at the used channels, note the special features of those inputs outlined below:
Measuring range 1 V to 5 V: wire the used and unused inputs of the same channel group
in parallel.
Current measurement, 2-wire transmitter: There are two ways to wire the channel circuit:
a) Open unused input; channel group diagnostics disabled. If you were to enable
diagnostics, the analog module would trigger a single diagnostic interrupt, and light up its
SF LED.
b) Terminating the unused input using a 1.5 kΩ to 3.3 kΩ resistor. This allows you to
enable diagnostics for this channel group.
Current measurement 4 mA to 20 mA, 4-wire transducer: wire the unused inputs of the
same channel group in series.
Wirebreak monitoring
The wire-break check function is designed only for temperature measurements
(thermocouples and thermoresistors.)
Special features of the wire-break check function in the 4 mA to 20 mA measuring range
If you configured a measuring range of 4 mA to 20 mA, and enabled wire-break check, the
analog input module logs a wire-break event in diagnostics data when the current drops
below 3.6 mA.
The module also triggers a diagnostic interrupt if you enabled diagnostics interrupts in the
program.
The lit SF LED is otherwise the only indication of the wire-break, and you must evaluate the
diagnostic bytes in the user program.
If you configured a measuring range of 4 mA to 20 mA, disabled wire-break check, and
enabled diagnostic interrupts, the module triggers a diagnostic interrupt when the underflow
value is reached.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals