Analog modules
6.3 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF00-0AB0)
S7-300 Automation System Module data
6-8 Manual, 08/2006, A5E00105505-04
6.3 6.3 Analog input module SM 331; AI 8 x 16 Bit; (6ES7331-7NF00-0AB0)
Order number
6ES7331-7NF00-0AB0
Properties
8 inputs in 4 channel groups
Measuring method adjustable per channel group
Voltage
Current
Resolution adjustable per channel group (15 bits + sign)
Any measuring range selection per channel group
Programmable diagnostics and diagnostic interrupt
Limit value monitoring adjustable for 2 channels
Hardware interrupt can be set when limit exceeded
High-speed refreshing of measured values
Electrically isolated to the CPU
Resolution
The measured value's resolution is not dependent on the integration time selected.
Diagnostics
For information on diagnostics message consolidated at the "group diagnostics" parameter,
refer to the table
Diagnostics messages of analog input modules
.
Hardware interrupts
You can set the hardware interrupts of channel groups 0 and 1 in
STEP 7
. However, always
set a hardware interrupt only for the first channel of a channel group, i.e. either at channel 0,
or at channel 2
High-speed refreshing of measured values
In high-speed refresh mode, the measured values at two channels of a group occur are
refreshed three times faster than those at multiple active channel groups.
Example: Channels 0 and 1 are active with 2 ms filtering. Refreshed data are thus available
at intervals of 10 ms to the PLC at both channels. (For other settings, the refresh rate is
equivalent to the filter setting.)
A high-speed update of measured values is only possible if both channels of channel group
0 and 1 are active, i.e. the "measuring method" parameter is set. However, only one of the
two channel groups 0 or 1 may be active (not concurrently active.)

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals