Analog modules   
6.15 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; (6ES7334-0CE01-0AA0) 
  S7-300 Automation System Module data 
6-130  Manual,  08/2006, A5E00105505-04 
6.15  6.15 Analog IO module SM 334; AI 4/AO 2 x 8/8 Bit; 
(6ES7334-0CE01-0AA0) 
Order number 
6ES7334-0CE01-0AA0 
Properties 
●  4 inputs in one group and 2 outputs in one group 
●  Resolution 8 bits 
●  Measuring method adjustable per channel group 
–  Voltage 
–  Current 
●  Not programmable, measurement and output type defined by hardwiring 
●  Non-isolated to the backplane bus interface 
●  Electrically isolated to load voltage 
Terminal assignment 
The following diagrams show wiring examples. 
 
 
Note 
Note when wiring the SM 334: 
•  analog ground  M
ANA
(terminal 15 or 18) is connected to chassis ground M of the CPU or 
interface module IM. Use a cable with a conductor cross-section of at least 1 mm
2
. 
The module will shut down if the ground connection between M
ANA
 and M is missing. 
Inputs are read with 7FFF
H
, and outputs return a value of 0. The module may be 
destroyed if operated without ground over a longer period of time. 
•  the supply voltage for the CPU and/or the interface module (IM) may not be connected 
with reversed polarity. Reverse polarity will inevitably lead to the destruction of the 
module, because M
ANA
 develops an impermissible high potential (+24 V.)