Priniples of analog value processing
4.7 Connecting loads/actuators to analog outputs
S7-300 Automation System Module data
4-20 Manual, 08/2006, A5E00105505-04
4.7 4.7 Connecting loads/actuators to analog outputs
Connecting loads/actuators to analog outputs
The analog output modules can be used to supply power to loads and actuators.
Cables for analog signals
Always use shielded twisted-pair cables to wire analog signals. Form two twisted pairs of the
Q
V
and S+, and M and S- signals in order to reduce interference. Connect both ends of the
analog cable shield to ground.
Any potential difference between the cable ends may cause an equipotential current on the
shield, and thus disturbance on analog signals. To avoid this situation, you should ground
the shield only at one end of the cable.
Electrically isolated analog output modules
When using electrically isolated analog output modules, the reference point of measuring
circuit M
ANA
and the CPU's M terminal are not galvanically interconnected.
Always use electrically isolated analog input modules if there is a risk of a potential
difference V
iso
developing between the reference point of measuring circuit M
ANA
and the M
terminal of the CPU. Use an equipotential bonding conductor to interconnect the M
ANA
terminal and the M terminal of the CPU, in order to prevent V
iso
from exceeding the permitted
value.
Non-isolated analog output modules
When using on-isolated analog output modules, always interconnect the reference point
M
ANA
of the of measuring circuit with terminal M of the CPU. Wire the M
ANA
terminal to the M
terminal of the CPU. Any potential difference between M
ANA
and the M terminal of the CPU
could otherwise corrupt the analog signal.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals