EasyManua.ls Logo

Siemens SIMATIC S7-300 Module data - Parameters of SM 321; DI 16 X DC 24 V

Siemens SIMATIC S7-300 Module data
594 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital modules
3.10 Digital input module SM 321; DI 16 x 24 VDC; with hardware and diagnostic interrupts
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
3-27
3.10.2 Parameters of SM 321; DI 16 x DC 24 V
Programming
The general procedure for programming digital modules is described in
Configuring digital
modules
.
Parameters of SM 321; DI 16 x DC 24 V
The table below shows an overview of configurable parameters and their default settings for
SM 321; DI 16 x DC 24 V.
The default settings apply if you have not set any parameters in STEP 7.
Table 3-8 Parameters of SM 321; DI 16 x DC 24 V
Parameters Range of values Default Parameter
type
Scope
Enable
• Diagnostic interrupt
• Hardware interrupt
Yes/no
Yes/no
No
No
Dynamic
Module
Input delay/voltage type 0.1 ms (DC)
0.5 ms (DC)
3 ms (DC)
15 ms (DC)
20 ms (DC/AC)
(DC) static Module
Diagnostics
• Encoder supply missing
• Wirebreak
Yes/no
Yes/no
No
No
static
Channel group
Hardware interrupt trigger
• Positive edge
• Negative edge
Yes/no
Yes/no
No
No
Dynamic
Channel group
Allocating the encoder supplies to channel groups
The module's two encoder supplies, supply power to two channel groups: Inputs 0 to 7 and
inputs 8 to 15. You also configure diagnostics for the encoder supply at those two channel
groups.
(6ES7321-7BH01-0AB0)