General technical data
1.1 Standards and certifications
S7-300 Automation System Module data
1-4 Manual, 08/2006, A5E00105505-04
Marine approvals
Classification Societies:
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
Use in industry
SIMATIC products are designed for industrial applications.
Table 1-1 Use in industry
Field of
application
Noise emission requirements Noise immunity requirements
Industry EN 61000-6-4: 2001 EN 61000-6-2: 2001
Use in residential areas
To operate an S7-300 in a residential area, it's RF emission must comply with Limit Value
Class B to EN 55011.
Suitable measures for achieving RF suppression to Limit Value Class B:
S7-300 installation in grounded switch cabinets / cubicles
Use of noise filters in the supply lines
Warning
There is a risk of injury or of damage to assets.
In potentially explosive environments, there is a risk of injury or damage if you disconnect
any connectors while the S7-300 is in operation.
Always isolate the S7-300 operated in such areas before you disconnect and connectors.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)