Description of system components
8.3 Operator panel with display
SIMOCODE pro
120 System Manual, 05/2019, A5E40507475002A/RS-AD/004
8.3.3.7 Status display for fieldbus communication
The "Communication" menu item displays all important information concerning fieldbus
communication.
PROFIBUS/Modbus:
In addition to the current PROFIBUS/Modbus device address, the baud rate or
fieldbus-relevant settings concerning process and diagnostic alarms to the automation
system.
These are the most important menus by way of example:
PROFIBUS/Modbus address
PROFIsafe address: Indicates the PROFIsafe address (only for OPD versions as from
*E04*, SIMOCODE pro V PB basic unit as from *E07* and an available with a
DM-F PROFIsafe)
Baud rate
Bus ok, Bus monitoring
PLC/PCS in Run, PLC/PCS monitoring
Bus/PLC fault - reset
Startup parameter block
Time stamping active
Compatibility mode
Compatibility mode 1, 3UF50 Mode
3UF50 mode DPV0, DPV1
3UF50 basic type
Diagnostics device error, diagnostics message: Displays which diagnostic information of
type "device error" and/or "message" is sent by SIMOCODE pro to a higher-level
automation system via PROFIBUS.
Diagnostics warning, diagnostics trip: Displays which diagnostic information of type
"warning" and/or "trip" is sent by SIMOCODE pro to a higher-level automation system via
PROFIBUS.