Commissioning, service, troubleshooting
13.2 Commissioning
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
271
13.2.4.2 Setting IP parameters and EIP device name
Setting IP parameters and device name on a plant-specific basis
For communication via EtherNet/IP it is mandatory to set the IP parameters and the device
name.
These parameters can be set in different ways, depending on the needs of the plant
configuration.
Setting IP parameters and EtherNet/IP device name with SIMOCODE ES via PC cable
Proceed as follows:
Table 13- 13 Setting IP parameters and EtherNet/IP device name with SIMOCODE ES via PC cable
Step
Description
1
Plug the PC cable into the system interface
2
Start SIMOCODE ES (TIA Portal)
3 1st option: Create new project
In the Project view, create a new project via "Project New"
Add a new device by double-clicking the button "Add new device"
in the project navigator and select the application in the device
wizard. The selected application corresponds to the description in
the manual SIMOCODE pro - Application examples
(https://support.industry.siemens.com/cs/ww/en/view/109743959
)
.
Check the device configuration and adapt it to the actual
configuration, if applicable
Select the communication settings under "Parameters Ethernet
parameters" and set the IP parameters and the device name
Under "Parameters Motor protection", set the current setting
and, if applicable, other parameters
Adapt other parameters in the parameter editor if necessary
Save the project and transfer the device parameters to the device
2nd option: Do not create a new project
In the portal view, click on the button
"Online & Diagnostics"
Click "Accessible devices". The
"Accessible devices" window opens
Click the "Start search" button
Select a station
4 Select the type of the PG/PC interface (SIRIUS PtP in this case)
5 Select the PG/PC interface via which the USB PC cable is
connected to the computer.
6 Click on the "Start search" button and load the parameterization into
the device.
After successfully transferring the parameters into the device (see
message in inspector window), the device is ready to operate.
7 Select a suitable station. You can show the following
devices/stations:
devices with the same addresses
all compatible stations
accessible stations