Technical data
15.11 Typical reaction times
SIMOCODE pro
366 System Manual, 05/2019, A5E40507475002A/RS-AD/004
Example:
You wish to switch a relay output of the basic unit via PROFIBUS when the "remote" bit is
set:
SIMOCODE pro C: Reaction time = 30 ms + 30 ms + 10 ms = 70 ms
SIMOCODE pro V: Reaction time = 5 ms + 5 ms + 10 ms = 20 ms.
For the data from and to the PLC, you must also add the times for bus execution time, IM/CP
cycles, and PLC-CPU cycle.
You will find the corresponding information in the device descriptions.
2) 2nd generation current / voltage measuring modules
3) + set delay
4) Existing values are valid in compatibility mode
15.11.2 Typical response times of SIMOCODE pro S device series
Table 15- 3 Typical reaction times of the SIMOCODE pro device series
Component/control function
Time inputs
Time: Processing
Time: Outputs
Basic unit:
Thermistor:
PROFIBUS:
Set delay time
400 ms
30 ms
30 ms 10 ms
-
30 ms
Current measurement
Internal ground fault
300 ms
300 ms ... 600 ms + set delay
-
-
Multifunction module
24 V-DC version
110 V - 240 V AC/DC version
30 ms + delay time
65 ms + delay time
40 ms
40 ms
Ground-fault module function
100 ms + set delay
-
Temperature module function
500 ms
-
Star-delta starter - typical switchover
time from star to delta
100 to 150 ms
1)
-
1) QE2 and QE3 must be parameterized to the outputs of the basic unit.
Example:
You wish to switch a relay output of the basic unit via PROFIBUS when the "remote" bit is
set:
Reaction time = 30 ms + 30 ms + 10 ms = 70 ms
In the case of the data from and to the PLC, you must also add the times for bus runtime,
IM/CP cycles, and PLC-CPU cycle.
You will find the corresponding information in the device descriptions.