SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
337
15.3
Technical data
15.3 Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units
Technical specifications of the SIMOCODE pro V PN /
pro V PN GP / pro V EIP basic units
Technical specifications of the SIMOCODE pro V PN / pro V PN GP / pro V EIP basic units
Mounting Snap-mounted onto 35-mm standard mounting rail or screw-mounted
using additional push-in lugs
Mounting position
Any
Display
Red/green/yellow "DEVICE" LED
Red: "Function test negative, device disabled"
Green: "Ready for operation"
Yellow: "Memory module detected"
OFF: "No control supply voltage"
Green "BUS" LED
Continuous light: "Communication with PLC/PCS"
Flashing: "Baud rate recognized/communication with PC/PG"
Red "GEN. FAULT" LED
Continuous light/flashing: "Feeder fault", e.g. overload tripping
Green "PORT1" LED
Continuous light: Ethernet connection available
Flashing: Station flash test
Green "PORT2" LED
Continuous light: Ethernet connection available
Flashing: Station flash test
"TEST/RESET" button
Resets the device after tripping
Function test (system self-test)
Operation of memory module
System interfaces
Front For connecting an operator panel or expansion modules. The memory
module or a PC cable can also be connected to the system interface for
parameterization purposes.
Bottom Connection of a current measuring module or a current/voltage
measuring module
ETHERNET interface
Connection system
2 x RJ45 (LAN)
Transmission rate
Max. 100 Mbit/s
Number of interfaces according to PROFINET 2
1 (SIMOCODE pro V PN GP 3UF7011-1A.00-2 basic units)
PROFINET conformity class
B
Protocols supported PROFINET IO, PROFIsafe, LLDP, SNMP,
Address Resolution Protocol (ARP), HTTP, HTTPS, OPC UA Server,
NTP
Autonegation Yes
Autosensing Yes
MRP/MRRP redundancy procedure Yes
No (SIMOCODE pro V PN GP 3UF7011-1A.00-2 basic units)