Commissioning, service, troubleshooting
13.2 Commissioning
SIMOCODE pro
258 System Manual, 05/2019, A5E40507475002A/RS-AD/004
13.2.1.2 Setting the PROFIBUS DP address
Setting the PROFIBUS DP address via the addressing plug
Note
This setting cannot be made if t
he TEST / RESET button has been blocked.
Proceed as follows:
Table 13- 3 Setting the PROFIBUS DP address via the addressing plug
Step
Description
1 Set the desired valid address on the DIP switch.
The switches are numbered.
For example, address 21: Put the "16"+"4"+"1" switches in the "ON" position.
2
Plug the addressing plug into the system interface. The "Device" LED lights up yellow.
3 Briefly press the TEST / RESET button. The address you set is now stored. The "Device" LED flashes yellow for
approx. 3 seconds.
4
Remove the addressing plug from the system interface.
Setting the PROFIBUS DP address via SIMOCODE ES (TIA Portal)
Proceed as follows:
Table 13- 4 Setting the PROFIBUS DP address via SIMOCODE ES (TIA Portal)
Step
Description
1
Switch on the power supply of the basic unit.
2 Connect the USB interface of the PC/PG and the system interface of the basic unit to the Sirius USB PC cable. It
may be necessary to install a device driver for the parameterization cable when using the USB PC cable for the
first time.
3 Observe the status LED on the basic unit. The "Device" LED should light up green.
SIMOCODE pro can be started up.
4a Setting the address of a device configured in SIMOCODE ES (TIA Portal) (as started in steps 2 and 3):
Under "Parameters Fieldbus interface", set the "Station address" to the required address and then download the
parameterization to the device.
4b Setting the address of a SIMOCODE device without integration in the current project:
In the project navigator, open "Online access" via "Online & Diagnostics". Here, the device currently connected to
the serial interface can be accessed using "COM<x> [SIRIUS PtP] Update accessible devices". If the serial
interface COM<x> should indicate a protocol other than SIRIUS PtP, you can change this via the context menu
(right mouse button) Properties. There, under "Parameters Fieldbus interface", set the "Station address" to
the required address and then download the change into the device again.
5 After the parameters have been transferred to the basic unit, the message confirming successful downloading
appears under "Info General" in the status window.
Setting the PROFIsafe address on DM-F PROFIsafe
See Chapter "Safety-related tripping" in the manual Parameterizing SIMOCODE pro
(https://support.industry.siemens.com/cs/ww/en/view/109743958
).