Commissioning, service, troubleshooting
13.2 Commissioning
SIMOCODE pro
264 System Manual, 05/2019, A5E40507475002A/RS-AD/004
13.2.2.4 Diagnostics via LED display on the basic unit and on the operator panel (PROFINET)
The basic unit and the operating panel have LEDs for displaying specific device states:
Table 13- 8 Diagnostics via LED display
LED
Status
Display
Description
Corrective measures for faults
Device Device
status
Green
Device ON
_
Green
flickering
Internal fault Send the basic unit in for repair
Yellow Memory module recognized,
TEST/RESET buttons control the memory
module
_
Yellow flashing Memory module read in; factory settings
configured (duration: 3 s)
_
Yellow
flickering
Memory module programmed
(duration: 3 s)
_
Red
Device defective (also GEN. FAULT on)
Replace the basic unit!
Red flashing Memory module or expansion modules
defective (also GEN. FAULT on - flashing)
Reprogram/replace the memory
module, replace the expansion
modules
Off Supply voltage too low Check whether the supply
voltage is connected/switched on
Green - flashing
PE energy saving mode active
_
Bus Bus status Off No communication with the IO Controller
of the PLC/PCS via PROFINET
Connect the bus or check
PROFINET parameters (IP
parameters, device name)
Green Communication with the IO Controller of
the PLC/PCS via PROFINET is active
_
GEN.
FAULT
Fault
status
Red
Fault pending; reset has been saved
Rectify fault, e.g., overload
Red flashing Fault pending; reset has not been saved Clear the error and reset.
Configuration error: Parameterize
again and reset, or switch the
control voltage off and on again
Off
No fault
_
PORT1
(only on
basic unit)
Bus status
Green
Ethernet connection available
_
Off No Ethernet connection available Check the Ethernet connection
and the wiring
Flashing
Station flash test for device location active
_
PORT2
(only on
basic unit)
Bus status
Green
Ethernet connection available
_
Off No Ethernet connection available Check the Ethernet connection
and the wiring
Flashing
Station flash test for device location active
_