Description of system components
8.14 Configuration information for SIMOCODE pro V when using an older basic unit
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
157
Table 8- 8 Maximum configuration with expansion modules when using an operator panel/operator panel with display, a
2nd generation current/voltage measuring module and a SIMOCODE pro V-PB basic unit with a product
version earlier than E15 / SIMOCODE pro V Modbus basic unit with product version E01
SIMOCODE pro basic unit
U
s
= 24 V DC
SIMOCODE pro basic unit
U
s
= 110-240 V AC/DC
OP Measur
ement
DM-
F/DM
DM AM TM EM DM-
F/DM
DM AM TM EM
None/UI
Max. 4 modules
OP U/I
Max. 4 modules
1)
- - - -
OPD U/I
Max. 3 modules
1)
Max. 2 modules
1)
-
-
-
-
-
-
-
-
-
1) Max. 1 AM, TM, EM module
Note
Decoupling module
A decoupling module is not
necessary for 2nd generation current/voltage measuring
modules.
Configuration instructions for the use of fail-safe expansion modules
In conjunction with DM-F Local and DM-F PROFIsafe fail-safe digital modules, the
expansion modules can be used as follows:
Fail-safe digital
module
Number of expansion
modules
Digital module 2
Analog module
Temperature
module
Ground-fault
module
DM-F Local
max. 4
DM-F PROFIsafe
max. 3
Note
Restrictions for the SIMOCODE pro V device series
The restrictions mentioned here apply to the SIMOCODE
pro V High Performance device
series with the following product versions:
SIMOCODE pro V PB: Before E15
SIMOCODE pro V PN: Before E10
SIMOCODE pro V MR: Before E03
Devices with the stated product versions or later can be used without restriction with an
operator panel with display and 2nd
generation current/voltage measuring modules.