Commissioning, service, troubleshooting
13.3 Service
SIMOCODE pro
278 System Manual, 05/2019, A5E40507475002A/RS-AD/004
Saving parameters from the basic unit to a SIMOCODE ES file
Proceed as follows:
Table 13- 17 Saving parameters to a SIMOCODE ES file
Step
Description
1.
Plug the PC cable into the system interface.
2. Start SIMOCODE ES.
3.
Create a new project via "Create new project".
4.
Switch to the project view.
5.
Go online, e.g. via "Online & Diagnostics" in the project navigator
6. Open the "Online access" menu in the project navigator and select the suitable interface by
double-clicking it.
7.
Double-click on "Update accessible devices".
8.
Select "Online Upload device as new station (hardware and software) ...".
9.
Save the project.
Note
This function will not be available if the TEST
/ RESET button has been disabled.
Saving parameters from a SIMOCODE ES file into the basic unit
Proceed as follows:
Table 13- 18 Saving parameters from a SIMOCODE ES file into the basic unit
Step
Description
1.
Plug the PC cable into the system interface.
2.
Start SIMOCODE ES.
3.
Open a project.
4.
Select Online Extended online connection.
5.
Select the type of the PG/PC interface (SIRIUS PtP or PN/IE).
6.
Select the PG/PC interface.
7. Click the "Start search" button. A search is made for compatible stations.
8.
Select a station.
9.
Load the parameters to the device via "Online Load to device".