EasyManua.ls Logo

Siemens SIMOCODE pro V MR

Siemens SIMOCODE pro V MR
408 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of system components
8.1 Basic units (BU)
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
83
SIMOCODE pro V PN GP basic unit
The SIMOCODE pro V PN GP General Performance basic unit for PROFINET is used in
combination with a current measuring module and an optional operator panel. It provides the
following expansion options by means of connecting an expansion module:
Increased device functionality with additional inputs and outputs
Connection of a residual current transformer
Connection of a temperature sensor.
The following motor control functions are supported:
Overload relay
Direct starter (direct-on-line starter) and reversing starter
Star-delta starter
Circuit breaker control (MCCB)
Control of a soft starter.
SIMOCODE pro V High Performance basic unit
The SIMOCODE pro V High Performance basic units are the fundamental components of
the SIMOCODE pro V device series and are used in combination with a current measuring
module or current / voltage measuring module and optional operator panel.
The following motor control functions are supported:
Overload relay
Direct starter (direct-on-line starter) and reversing starter
Star-delta starter, possibly combined with reversing starter
2 speeds, motors with separate windings (pole-changing starters), possibly combined
with reversing starter
2 speeds, motors with separate Dahlander windings, possibly combined with reversing
starter
Positioner control
Solenoid valve control
Circuit breaker control (MCCB)
Soft starter control, possibly combined with reversing starter
The SIMOCODE pro V High Performance basic units provide the following expansion
options not offered by the SIMOCODE pro C, SIMOCODE pro S and
SIMOCODE PRO V PN GP basic units:
Increased device functionality via various expansion modules according to need
Use of a current / voltage measuring module in place of a current measuring module
Additional inputs and outputs, as required
Larger number of inputs and outputs
Use of an operator panel with display in place of a standard operator panel.