Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Bits 12 … 15 of the 1st word of the parameter channel contain the request and response
identifier.
Table 6- 2 Request identifiers, control → inverter
2 Change parameter value (word) 1 7 / 8
Change parameter value (double word)
4 Request descriptive element
1)
3 7 / 8
2)
Request parameter value (field)
1)
2)
Change parameter value (field, word)
1)
2)
Change parameter value (field, double word)
1)
Request number of field elements
The required element of the parameter is specified in IND (2nd word).
The following request IDs are identical: 1 ≡ 6, 2 ≡ 7 3 ≡ 8.
We recommend that you use identifiers 6, 7, and 8.
Table 6- 3 Response identifiers, inverter → control
Transfer parameter value (word)
Transfer parameter value (double word)
Transfer descriptive element
1)
Transfer parameter value (field, word)
2)
Transfer parameter value (field, double word)
2)
Transfer number of field elements
7 Inverter cannot process the request.
In the most significant word of the parameter channel, the inverter sends an error
number to the control, refer to the following table.
8 No master controller status / no authorization to change parameters of the parame-
The required element of the parameter is specified in IND (2nd word).
2)
The required element of the indexed parameter is specified in IND (2nd word).
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB