Adapt fieldbus configuration
6.3 Communication via PROFINET
Configure communication with STARTER
STARTER provides a screen form to
set the communication with the
control system.
Open the dialog screen form
"Control_Unit/Communication/Commi
ssioning interface" and activate the
"Configure IP interfaces" tab
● Set the DHCP mode to 0 (factory
setting).
● Enter the device name, address,
gateway and the address for the
subnet mask.
● In the Activation field select “[2]
Save and activate configuration”.
● To activate the settings, you must
switch off the inverter power supply and then switch on again.
You can also enter or read out data using the expert list. You can find the corresponding
parameters in the number range r8909 … p8925
Installing GSDML
Procedure
To install the GSDML of the inverter into the configuring tool of your control system, proceed
as follows:
1. Save the GSDML to your PC .
– From the Internet: GSDML
(http://support.automation.siemens.com/WW/view/en/22339653/133100
).
– From your inverter:
Insert a memory card into the inverter.
Set p0804 = 12.
The inverter writes the GSDML as zipped file (*.zip) into directory
/SIEMENS/SINAMICS/DATA/CFG on the memory card.
2. Unzip the GSDML file to a folder on your computer.
3. Import the GSDML into the configuring tool of your control system.
You have now installed the GSDML.