Alarms, faults and system messages
10.4 Identification & maintenance data (I&M)
10.4
Identification & maintenance data (I&M)
I&M data
The inverter supports the following identification and maintenance (I&M) data.
I&M
data
Format
Explanation
Associated
parameters
Example for the
content
I&M0 u8[64] PROFIBUS
u8[54] PROFINET
Inverter-specific data, read only - See below
I&M1 Visible String [32] Plant/system identifier p8806[031] "ak12-
ne.bo2=fu1"
Visible String [22]
Location code
p8806[3253]
"sc2+or45"
I&M2 Visible String [16] Date p8807[015] "2013-01-21
16:15"
I&M3
Visible String [54]
Any comment
p8808[053]
-
I&M4 Octet String[54] Check signature to track chang-
es for Safety Integrated.
This value can be changed by
the user.
The test signature is reset to the
value generated by the machine
is p8805 = 0 is used.
p8809[053] Values of
r9781[0] and
r9782[0]
When requested, the inverted transfers its I&M data to a higher-level control or to a PC/PG
with installed STEP 7, STARTER or TIA-Portal.
I&M0
Designation
Format
Example for the
content
Valid for
PROFINET
Valid for
PROFIBUS
Manufacturer-specific
u8[10]
0000 hex
---
MANUFACTURER_ID u16 42d hex
(=Siemens)
ORDER_ID Visible String
[20]
„6SL3246-0BA22-
1FA0“
SERIAL_NUMBER Visible String
[16]
„T-R32015957“
HARDWARE_REVISION
u16
0001 hex
SOFTWARE_REVISION
char, u8[3]
„V“ 04.70.19
REVISION_COUNTER
u16
0000 hex
PROFILE_ID
u16
3A00 hex
PROFILE_SPECIFIC_TYPE
u16
0000 hex
IM_VERSION
u8[2]
01.02
IM_SUPPORTED
bit[16]
001E hex
Converter with control units CU240D-2
272 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB