Backing up data and series commissioning
8.3 Saving settings and transferring them using an operator panel
8.3
Saving settings and transferring them using an operator panel
Precondition
When the power supply is sw
itched on, you
can transfer the inverter settings to the IOP
or vice versa, transfer the IOP data to the
inverter.
Inverter → IOP
Procedure
To back up the settings on the IOP, proceed as follows:
1.
Connect the operator panel to the inverter.
2.
Start data transfer in the menu "UP/DOWNLOAD" -
"Drive to panel".
You have backed up the settings on the BOP-2.
IOP → inverter
Procedure
To transfer the settings to the inverter, proceed as follows:
1.
Connect the operator panel to the inverter.
2.
Start data transfer in the menu "UP/DOWNLOAD" -
"Panel to drive".
3.
Switch off the inverter power supply.
4.
Wait until all LEDs on the inverter go dark. Now
switch on the inverter power supply again. Your
settings only become effective after this power-on
reset.
You have transferred the settings to the inverter.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
229