Technical data
11.2 Performance ratings Power Module
11.2
Performance ratings Power Module
SINAMICS G120 D performance ratings
Table 11- 2 Power Module performance ratings
Feature
Specification
Line voltage & power
ranges
3 AC 380 V … 500 V ± 10 %
High Overload: 0.75 kW7.5 kW (1.0 hp10.0 hp)
Line specification Relative short-circuit voltage of a transformer u
k
≤ 1%
The specification only refers to the total instantaneous regenerative feed-
back, however not to the total connected power of all of the power mod-
ules connected to the same transformer.
Further information: FAQ
(http://support.automation.siemens.com/WW/view/en/34189181).
Output voltage
3 AC 0 V … line volage × 0.87 (max.)
Input frequency
47 Hz63 Hz
Output frequency
0 Hz240 Hz
cos φ
1.05
Converter efficiency
95 % … 97 %
Overload capability (HO)
2 x Nominal output current for 3 seconds followed by 1.5 x Nominal output
current for 57 seconds every 300 seconds
Inrush current
Less than rated input current
Pulse frequency
4 kHz (standard); 4 kHz … 16 kHz (in 2 kHz steps)
Electromagnetic compat-
ibility
Internal Class A filters according to EN 55011
Protection level
IP65 (when Power Module and Control Unit is fully assembled)
Temperature range
Standard CU: -10 °C … +40 °C (14 °F … 104 °F) - High Overload (HO)
Fail-Safe CU: 0 °C … +40 °C (32 °F 104 °F) - High Overload (HO)
Storage temperature -40 °C … +70 °C (-40 °F … 158 °F)
Humidity < 95% RH - non-condensing
Operational altitude
Up to 1000 m (3280 ft) above sea level without derating
Protection features Undervoltage, Overvoltage, Overload, Ground faults, Short circuit, Stall
prevention, Motor blocking protection, Motor overtemperature, Power
Module overtemperature, Parameter interlock
Standards
UL, cUL, CE, C-tick
CE mark Conformity with EC Low Voltage Directive 73/23/EEC and filtered ver-
sions also Electromagnetic Compatibility Directive 89/336/EEC
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
283

Table of Contents