Advanced commissioning
7.2 Inverter control
7.2.1.4
Analog inputs
Overview
Changing the
function of the analog input
1.
Define the analog input type using
parameter p0756 to voltage input
0 V … 10 V.
2.
Specify the function of the analog input
by interconnecting parameter p0755 with
a connector input CI of your choice.
Define the analog input type
The converter offers a series of default settings, which you can select using parameter
p0756:
AI 0
Unipolar voltage input
No sensor connected
0
V … +10 V
p0756[0]
=
0
8
AI 1
Unipolar voltage inputt
No sensor connected
0
V … +10 V
p0756[1]
=
0
8
You can define your own characteristic that matches your particular application. The linear
scaling characteristic is defined using two points (p0757, p0758) and (p0759, p0760).
Parameters p0757 p0760 are assigned to an analog input via their index, e.g. parameters
p0757[0]p0760[0] belong to analog input 0.
Figure 7-4 Scaling characteristics
Table 7- 3 Parameters for the scaling characteristic and wire break monitoring
Parameter
Description
p0757
x-coordinate of 1st characteristic point [V]
p0758
y coordinate of the 1st characteristic point [% of p200x]
p200x are the parameters of the reference variables, e.g. p2000 is the reference
speed.
p0759
x-coordinate of 2nd characteristic point [V]
p0760
y-coordinate of 2nd characteristic point [% of p200x]
p0761
Wire breakage monitoring response threshold
Converter with control units CU240D-2
122 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB