Installation
4.2 Electrical Installation
Feeder protection of individual inverters
If you install a separate 400-V feeder for each inverter, you must protect each feeder
individually.
Figure 4-5 Power supply to inverters through separate 400-V feeders
Feeder protection according to IEC
Table 4- 1 Feeder protection according to IEC
Max. rated
current of the
protection de-
vice
FSA 3NA3803 3RV2011-1JA10 10 A
FSC 3NA3807 3RV2021-4BA10 20 A
Feeder protection according to UL standards
Use in North America requires protection devices that meet UL standards as detailed in the
following tables.
Table 4- 2 Overview of the approved protection devices according to UL standards
Fuses of any manufacturer with faster tripping characteristic than class RK5, e.g.
class J, time, CC, G, or CF
JDDZ
Intrinsically safe SIEMENS circuit breaker
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
35