Adapt fieldbus configuration
6.3 Communication via PROFINET
Select telegram
PROFIdrive telegrams
The following telegrams are available:
=
1:
20:
350:
352:
353:
354:
999:
-2/2 (factory setting)
Standard telegram 20, PZD
-2/6
SIEMENS telegram 350, PZD
-4/4
SIEMENS telegram 352, PZD
-6/6
SIEMENS telegram 353, PZD
-2/2, PKW-4/4
SIEMENS telegram 354, PZD
-6/6, PKW-4/4
Extend telegrams and change signal interconnection (Page 99)
A more detailed depiction of the individual telegrams can be found in Section Cyclic
communication (Page 92).
Selecting a telegram
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.
Activating diagnostics via the control
The converter provides the functionality to transmit fault and alarm messages (diagnostic
messages) to the higher-level control according to the PROFIdrive error classes.
You must select the functionality in the higher-level control (see Manuals for your converter
(Page 316)) and activate it by booting up.
Converter with control units CU240D-2
110 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB