Installation
4.2 Electrical Installation
4.2.5
Feeder protection of multiple inverters
For installations with more than one inverter, the inverters are normally powered from a 400-
V power bus with a T distributor.
Figure 4-6 Power supply to an inverter group via a shared 400-V feeder
Calculation of the feeder protection according to IEC and UL standards
Calculation of the feeder protection:
Add together the rated input currents of the inverter group.
The sum of all rated input currents must be 24 A.
Use one of the following protection devices for the inverter group:
Fuse or circuit breaker with a rated current of 30 A
Intrinsically safe circuit breaker with a rated current of 25 A
The feeder protection also depends on the following conditions:
Type of cable routing
Limit values of the cables and system components, e.g. the T distributor.
Country-specific regulations
If it is precluded that all of the inverters of a group operate simultaneously, it is permissible to
form larger inverter groups on one 400-V feeder. The sum of the rated input currents of all of
the inverters operated simultaneously must always be less than 24 A.
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
37