Advanced commissioning
7.7 Application-specific functions
The load monitoring comprises the following components:
● Load failure monitoring
● Monitoring for torque deviation
● Speed deviation monitoring
If the load monitoring detects load failure, then the converter always goes into a fault
condition and outputs fault F07936. For a torque and speed deviation, as response, you can
either set an alarm or a fault. Details are provided in the following descriptions.
Table 7- 28 Setting options for load monitoring
p2193
Load monitoring configuration
(factory setting: 1)
0: Monitoring deactivated
1: Torque and load failure monitoring
2: Speed and load failure monitoring
3: Load failure monitoring
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
195