Adapt fieldbus configuration
6.3 Communication via PROFINET
Integrating inverters into PROFINET
Procedure
To connect the inverter to a control via PROFINET, proceed as follows:
1. Integrate the inverter in the bus system (e.g. ring topology) of the control using
PROFINET cables and the two PROFINET jacks X03 and X04.
The position of the jacks and the pin assignment can be found in Section Overview of the
interfaces (Page 34).
The maximum permitted cable length from the previous station and to the subsequent
one is 100 m.
2. Externally supply the inverter with 24 V DC through X01.
The external 24 V supply is only required if communications with the control should also
run when the mains voltage is switched off.
You have connected the inverter to the control using PROFINET.
Configuring communication to the control
Configuring the communication using SIMATIC S7 control
You have the following options, if the inverter is not included in the hardware library:
● Install the most up to date STARTER version
● Install the GSDML of the inverter using “Tools/Install GSDML file" in HW Config.
Additional information on this topic is provided in the "Fieldbuses" Function Manual, also see
Manuals for your converter (Page 316).
Configuring the communication using a non-Siemens control
1. Import the device file (GSDML) of the inverter into the engineering tool for your control
system.
2. Configure the communication.
Converter with control units CU240D-2