Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with ON/OFF1, you must assign parameter p0840[1] (source,
ON/OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter
channel as follows:
PKE, bit 12 … 15 (AK): = 7 hex
(change, parameter value (field, word))
PKE, bit 0 … 10 (PNU): = 348 hex
(840 = 348 hex, no offset, as 840 < 1999)
IND, bit 8 … 15 (subindex): = 1 hex
(CDS1 = index1)
IND, bit 07 (page index): = 0 hex
(offset 0
0 hex)
PWE1, bit 015
: =
2D2 hex
(722 = 2D2 hex)
PWE2, bit 1015: = 3F hex
(drive object - for SINAMICS G120, always 63 = 3f hex)
PWE2, bit 09: = 2 hex
(index of parameter (DI 2 = 2))
Figure 6-6 Telegram, to assign DI 2 with ON/OFF1
"Reading and writing parameters" application example
See: Reading and writing parameters via PROFIBUS
(http://support.automation.siemens.com/WW/view/en/8894584
).
6.2.1.5
Slave-to-slave communication
"Direct data exchange" is sometimes called "slave-to-slave communication" or "data
exchange broadcast". Here, slaves exchange data without any direct involvement of the
master.
You can find more information in: "Manuals for your inverter in the fieldbus function manual
(Page 316)".
6.2.2
Acyclically reading and writing inverter parameters
The inverter supports the writing and reading of parameters via acyclic communication:
For PROFIBUS: Up to 240 bytes per write or read request via data set 47
For PROFINET: Write or read requests via B02E hex and B02F hex
You will find more information on acyclic communication in the Fieldbus Function Manual;
see also section: Manuals for your converter (Page 316).
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
105

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120D Series and is the answer not in the manual?

Siemens SINAMICS G120D Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G120D Series
CategoryMedia Converter
LanguageEnglish

Related product manuals