Adapt fieldbus configuration
6.2 PROFIdrive profile for PROFIBUS and PROFINET
Telegram examples
Read request: Read out serial number of the Power Module (p7841[2])
To obtain the value of the indexed parameter p7841, you must fill the telegram of the
parameter channel with the following data:
PKE, bit 12 … 15 (AK): = 6
(request parameter value (field))
PKE, bit 0 … 10 (PNU): = 1841
(Parameter number without offset)
Parameter number = PNU + offset (page index)
(7841 = 1841 + 6000)
IND, bit 815 (subindex): = 2
(Index of the parameter)
IND, bit 07 (page index): = 90 hex
(offset 6000
90 hex)
Because you want to read the parameter value, words 3 and 4 in the parameter channel
for requesting the parameter value are irrelevant. They should be assigned a value of 0,
for example.
Figure 6-4 Telegram for a read request from p7841[2]
Write request: Change restart mode (p1210)
The restart mode is inhibited in the factory setting (p1210 = 0). In order to activate the
automatic restart with "acknowledge all faults and restart for an ON command", p1210 must
be set to 26:
PKE, bit 12 … 15 (AK): = 7
(change parameter value (field, word))
PKE, bit 0 … 10 (PNU): = 4BA hex
(1210 = 4BA hex, no offset, as 1210 < 1999)
IND, bit 815 (subindex): = 0 hex
(parameter is not indexed)
IND, bit 0 … 7 (page index): = 0 hex
(offset 0
corresponds to 0 hex)
PWE1, bit 015: = 0 hex
PWE2, bit 015: = 1A hex
(26 = 1A hex)
Figure 6-5 Telegram, to activate the automatic restart with p1210 = 26
Converter with control units CU240D-2
104 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB