Corrective maintenance
9.1 Replacing inverter components
9.1.6
Replacing a Control Unit with active know-how protection
Replacing devices with know-how protection without copy protection
In the case of know-how protection without copy protection, the inverter settings can be
transferred to another inverter using a memory card.
See also:
Saving settings to the memory card (Page 221)
Transferring the settings from the memory card (Page 222)
Replacing devices with know-how protection with copy protection
The know-how protection with copy protection prevents the inverter settings from being
copied and passed on. This function is predominantly used by machine manufacturers.
If know-how protection with copy protection is active, the inverter cannot be replaced as
described in "Overview of replacing converter components (Page 238)."
However, to allow the inverter to be replaced, you must use a Siemens memory card, and
the machine manufacturer must have an identical machine that he uses as sample.
There are two options for replacing the device:
Option 1: The machine manufacturer only knows the serial number of the new inverter
The end customer provides the machine manufacturer with the following information:
For which machine must the inverter be replaced?
What is the serial number (r7758) of the new inverter?
The machine manufacturer goes online on the sample machine.
deactivates the know-how protection, see Settings for know-how protection
(Page 234)
enters the serial number of the new inverter in p7759
enters the serial number of the inserted memory card as reference serial number in
p7769
activates the know-how protection with copy protection ("Copy RAM to ROM" must be
activated!), see Settings for know-how protection (Page 234)
writes the configuration with p0971 = 1 to the memory card
sends the memory card to the end customer
The end customer inserts the memory card and switches on the inverter.
When powering up, the inverter checks the serial numbers of the card and when there is a
match, the inverter goes into the "ready to start" state.
If the numbers do not match, then the inverter signals fault F13100 (no valid memory card).
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB
247

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120D Series and is the answer not in the manual?

Siemens SINAMICS G120D Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G120D Series
CategoryMedia Converter
LanguageEnglish

Related product manuals