Corrective maintenance
9.1 Replacing inverter components
Option 2: The machine manufacturer knows the serial number of the new inverter and the
serial number of the memory card
The end customer provides the machine manufacturer with the following information:
For which machine must the inverter be replaced?
What is the serial number (r7758) of the new inverter?
What is the serial number of the memory card?
The machine manufacturer goes online on the sample machine.
deactivates the know-how protection, see Settings for know-how protection
(Page 234)
enters the serial number of the new inverter in p7759
enters the serial number of the customer's memory card as reference serial number in
p7769
activates the know-how protection with copy protection ("Copy RAM to ROM" must be
activated!), see Settings for know-how protection (Page 234)
writes the configuration with p0971 = 1 to the memory card
copies the encrypted project from the card to his PC
for example, sends it by e-mail to the end customer
The end customer copies the project to the Siemens memory card that belongs to the
machine, inserts it in the inverter and switches on the inverter.
When powering up, the inverter checks the serial numbers of the card and when there is a
match, the inverter goes into the "ready to start" state.
If the numbers do not match, then the inverter signals fault F13100 (no valid memory card).
Converter with control units CU240D-2
248 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB