Installation
4.2 Electrical Installation
In one installation, either the inverters of group ① or the inverters of group ② are in
operation, but never both groups
① and ② simultaneously.
Figure 4-7 Protection of two inverter groups via a shared 400-V feeder
The sum of the rated input currents is:
● Group
①: 7.2 A + 7.2 A + 9.5 A = 23.9 A ≤ 24 A
● Group
①: 17.7 A + 3.8 A + 2.1 A = 23.6 A ≤ 24 A
You can power all the inverters through a shared fuse.
Feeder protection according to IEC
Table 4- 5 Feeder protection according to IEC
Max. rated current of the protec-
tion device
Article No. of the circuit breaker
25 A 3NA3810 3RV2021…, 3RV1031…,
3RV2031…
Feeder protection according to UL standards
Use in North America requires protection devices that meet UL standards as detailed in the
following tables.
Table 4- 6 Overview of the approved protection devices according to UL standards
Fuses of any manufacturer with faster tripping characteristic than class RK5, e.g.
class J, time, CC, G, or CF
JDDZ
Intrinsically safe SIEMENS circuit breaker
Converter with control units CU240D-2
38 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB