Technical data
11.1 Performance ratings Control Unit
Feature
Specification
Fail-safe input
DI 4 and DI 5 form the fail-safe digital input.
Maximum input voltage 30 V, 5.5 mA
Response time:
Typical: 5 ms + debounce time p9651
Typical, if debounce time = 0: 6 ms
Worst-case scenario: 15 ms + debounce time
Worst case, if debounce time = 0: 16 ms
You will find the extended function data in the Safety Integrated Func-
tion Manual.
PFH 5 × 10E-8
Probability of failure of the fail-safe functions (Probability of Failure per
Hour)
USB interface
Mini-B (not available on the push-pull variants of the control unit)
Note
Short-term voltage dips in the external 24 V supply (≤ 3 ms and ≤ 95% of the rated voltage)
When the mains voltage of the inverter is switched off, the inverter responds to short
-term
voltage dips in the external 24 V supply with fault F30074. Commu
nication via fieldbus,
however, remains in effect in this case.
Converter with control units CU240D-2
282 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB