Technical data
11.2 Performance ratings Power Module
Feature
Specification
Brake voltage 180 V DC (400 V half-wave rectified) 1 A maximum
The UL approved current rating for the brake output is 600 mA.
Standby current If the converter is powered-up, but the motor is still switched off, the con-
verter requires a standby current.
You have to consider the standby current when calculating the size of the
conductors and selecting the correct protective devices on the line supply.
For more comprehensive information on the standby current, please read
the following FAQ: Standby currents for PM250D
(http://support.automation.siemens.com/WW/view/en/31764702).
Converter with control units CU240D-2
284 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB