Adapt fieldbus configuration
6.4 Communication via PROFIBUS
PROFIdrive telegrams
The following telegrams are available:
p0922
=
1:
20:
350:
352:
353:
354:
999:
Standard telegram 1, PZD
-2/2 (factory setting)
Standard telegram 20, PZD
-2/6
SIEMENS telegram 350, PZD
-4/4
SIEMENS telegram 352, PZD
-6/6
SIEMENS telegram 353, PZD
-2/2, PKW-4/4
SIEMENS telegram 354, PZD
-6/6, PKW-4/4
Cyclic communication (Page 92)
A more detailed depiction of the individual telegrams can be found in Section Extend
telegrams and change signal interconnection (Page 99).
Selecting a telegram
Procedure
Proceed as follows to set a specific telegram in the inverter:
Using STARTER or an operator panel, set parameter p0922 to the appropriate value.
You have set a specific telegram in the inverter.