Advanced commissioning
7.2 Inverter control
Table 7- 1 Binector inputs (BI) of the inverter (selection)
BI
Significance
BI
Significance
p0810
Command data set selection CDS bit 0
p1036
Motorized potentiometer, setpoint, lower
p0840 ON/OFF1 p1055 Jog bit 0
p0844
OFF2
p1056
Jog bit 1
p0848 OFF3 p1113 Setpoint inversion
p0852
Enable operation
p1201
Flying restart enable signal source
p0855
Unconditionally release holding brake
p2103
1. Acknowledge faults
p0856
Enable speed controller
p2106
External fault 1
p0858
Unconditionally close holding brake
p2112
External alarm 1
p1020
Fixed speed setpoint selection bit 0
p2200
Technology controller enable
p1021 Fixed speed setpoint selection bit 1 p3330 Two-wire/three-wire control, control
command 1
p1022 Fixed speed setpoint selection bit 2 p3331 Two-wire/three-wire control, control
command 2
p1023 Fixed speed setpoint selection bit 3 p3332 Two-wire/three-wire control, control
command 3
p1035
Motorized potentiometer, setpoint, raise
A complete list of the binector outputs is provided in the List Manual.
Changing the function of a digital input - example
In order to switch on the motor with digital input DI
2, you
have to connect the status parameter of DI
2 to p0840: Set
p0840 = 722.2.
Advanced settings
You can debounce the digital input signal using parameter p0724.
For more information, see the parameter list and the function block diagrams 2210 ff of the
List Manual.
Analog inputs as digital inputs
When required, you can use the analog inputs as additional digital inputs.
Figure 7-3 Additional digital inputs
Converter with control units CU240D-2
118 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB