Advanced commissioning
7.5 Motor control
3. The inverter accelerates the motor.
During measurement, the inverter signals the warning A07961.
When the inverter has determined all the intermediate points of the friction characteristic
without fault code F07963, the inverter stops the motor.
You have recorded the friction characteristic.
Interconnect the precontrol of the speed controller with the frictional torque
To interconnect the precontrol of the speed co
n-
troller with the frictional torque, set p1
513 =
r3841 (frictional torque = additional torque 2).
You will find additional information in function
diagram 6060 of the List Manual.
p3820
…
Intermediate points of the friction characteristic [rpm; Nm]
r3840
Friction characteristic status word
1 signal: Friction characteristic OK
1 signal: Determination of the friction characteristic is active
1 signal: Determination of the friction characteristic is complete
1 signal: Determination of the friction characteristic has been aborted
1 signal: Friction characteristic positive direction
Friction characteristic, output [Nm]
p3842
Activate friction characteristic
0: Friction characteristic deactivated
1: Friction characteristic activated
p3845
Activate friction characteristic plot
(factory setting: 0)
0: Friction characteristic plot deactivated
1: Friction characteristic plot activated, both directions
2: Friction characteristic plot activated, positive direction
3: Friction characteristic plot activated, negative direction
p3846
Friction characteristic plot ramp-up/ramp-down time
(factory setting: 10 s)
Ramp-up/ramp-down time for automatic plotting of the friction characteristic.
p3847
Friction characteristic plot warm-up period
(factory setting: 0 s)
At the start of automatic plotting, the inverter accelerates the motor up to the speed =
p3829 und keeps the speed constant for this time.
You will find more information in the List Manual.
Converter with control units CU240D-2
158 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB