Advanced commissioning
7.5 Motor control
p1226
Standstill detection, speed threshold
(Factory setting: 20 rpm)
The moment of inertia estimator only measures the load torque for speeds ≥ p1226.
p1226 also defines from which speed the inverter switches-off the motor for OFF1
p1560
Moment of inertia estimator accelerating torque threshold value
(factory setting:
p1561
Moment of inertia estimator change time
inertia (factory setting: 500 ms)
The lower that p1561 or p1562 is, the
shorter the moment of inertia estimator
measurements.
The larger p1561 or p1562 is, the
more accurate the results provided by
the moment of inertia estimator.
p1562
Moment of inertia estimator change time
load
(factory setting: 10 ms)
p1563
Moment of inertia estimator load torque positive direction of rotation
(factory setting:
p1564
Moment of inertia estimator load torque negative direction of rotation
(factory setting:
p5310
Moment of inertia precontrol configuration (factory setting: 0000 bin)
1 signal: activates calculation of the characteristic (p5312 … p5315)
1 signal: activates moment of inertia precontrol
p5310.00 = 0, p5310.01 = 0
Deactivating moment of inertia precontrol
p5310.00 = 1, p5310.01 = 0
Adapting the moment of inertia precontrol
p5310.00 = 0, p5310.01 = 1 Activating the moment of inertia precontrol.
The characteristic of the moment of inertia
precontrol remains unchanged.
p5310.00 = 1, p5310.01 = 1
Activating the moment of inertia precontrol. The
inverter adapts the characteristic in parallel.
r5311
Moment of inertia precontrol status word
.00 1 signal: New measuring points for the characteristic of the moment of inertia
1 signal: new parameters are been calculated
1 signal: moment of inertia precontrol active
.03 1 signal: the characteristic in the positive direction of rotation has been calcu-
.04 1 signal: the characteristic in the negative direction of rotation has been calcu-
1 signal: The inverter writes actual results to the parameter
p5312
Moment of inertia precontrol linear positive
(factory
2
In a positive direction of rota-
tion:
Moment of inertia = p5312 ×
p5313
Moment of inertia precontrol constant positive
(fac-
2
p5314
Moment of inertia precontrol linear negative
(factory
2
In a negative direction of rota-
tion:
Moment of inertia = p5314 ×
p5315
Moment of inertia precontrol constant negative
2
Converter with control units CU240D-2
Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB