EasyManua.ls Logo

Siemens SINAMICS G120D Series - Page 218

Siemens SINAMICS G120D Series
326 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Advanced commissioning
7.9 Switchover between different settings
Table 7- 34 Parameters for switching the drive data sets:
Parameter
Description
p0820[0…n]
Drive data set selection DDS bit 0
If you use several command data sets
CDS, then you must set this parameter
for each CDS. The parameters are as-
signed to a CDS through their index:
CDS0: p0820[0], p0821[0]
CDS1: p0820[1], p0821[1]
p0821[0…n]
Drive data set selection DDS bit 1
p0826
Motor changeover, motor number
Each drive data set is assigned a motor number:
p0826[0] = motor number for drive data set 0.
p0826[3] = motor number for drive data set 3.
If yo
u operate the same motor with different drive data sets, then you must enter the
same motor number in every index of parameter p0826. In this particular case, you
can also switch over between the different drive data sets in operation.
If you operate different motors on one inverter, then you must number the motors in
parameter p0826. In this case, you may only switch over the drive data sets in the
"ready for operation" state with the motor switched-off. The switchover time is ap-
prox. 50 ms.
r0051
Displaying the number of the DDS that is currently effective
For an overview of all the parameters that belong to the drive data sets and can be switched,
see the List Manual.
Table 7- 35 Parameters for copying the drive data sets
Parameter
Description
p0819[0]
Source drive data set
p0819[1]
Target drive data set
p0819[2] = 1
Start copy operation
For more information, see the List Manual (the parameter list and function diagram 8565).
Converter with control units CU240D-2
218 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB

Table of Contents

Related product manuals