Alarms, faults and system messages
10.2 Faults
Extended settings for faults
Parameter
Description
You can modify the motor fault response for up to 20 different fault codes:
p2100
Setting the fault number for fault response
Selecting the faults for which the fault response should be changed
p2101
Setting, fault response
Setting the fault response for the selected fault
You can modify the acknowledgement type for up to 20 different fault codes:
p2126
Setting the fault number for the acknowledgment mode
Selection of the faults for which the acknowledgment type should be changed
p2127
Setting, acknowledgment mode
Setting the acknowledgment type for the selected fault
1: Can only be acknowledged using POWER ON
2: IMMEDIATE acknowledgment after removing the fault cause
You can change up to 20 different faults into an alarm, or suppress faults:
p2118
Setting the message number for the message type
Selection of the message for which the message type should be changed
p2119
Setting the message type
Setting the message type for the selected fault
1: Fault
2: Alarm
3: No message
You will find details in function diagram 8075 and in the parameter description of the List
Manual.