Alarms, faults and system messages
10.6 List of alarms and faults
Number
Cause
Remedy
A07922 Torque/speed out of tolerance
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
F07923
Torque/speed too low
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
F07924 Torque/speed too high
A07927
DC braking active
Not required
A07980
Rotary measurement activated
Not required
A07981 No enabling for rotary measure-
ment
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
A07991 Motor data identification activated Switch on the motor and identify the motor data.
F08501 Setpoint timeout
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the set monitoring time p2044.
F08502 Monitoring time sign-of-life expired
Check the PROFINET connection.
F08510
Send configuration data not valid
Check the PROFINET configuration
A08511 Receive configuration data not
valid
A08526 No cyclic connection
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
A08565 Consistency error affecting adjust-
able parameters
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
F08700 Communications faulty A CAN communications error has occurred. Check the following:
Bus cable
Baud rate (p8622)
Bit timing (p8623)
Masters
Start the CAN controller manually with p8608 = 1 after the cause of the
fault has been resolved!
F13100 Know-how protection: Copy protec-
tion error
The know-how protection and the copy protection for the memory card
are active. An error occurred during checking of the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
F13101 Know-how protection: Copy protec-
tion cannot be activated
Insert a valid memory card.
Converter with control units CU240D-2