Commissioning
5.3 Basic commissioning with IOP
11.
Input the correct Motor Speed from the motor
rating
plate.
This value is given in RPM.
12.
Select to run or disable Motor Data Identification fun
c-
tion.
This function, if active, will not start until the fi
rst run
command is given to the Inverter.
13.
Select either zero pulse on no zero pulse for the a
t-
tached encoder.
If no encoder is fitted to the motor, the optio
n will not be
displayed.
14.
Enter the correct pulses per revolution for the encoder.
This information is normally printed on the casing of the
encoder.
15.
Select the macro that is suitable for your application.
Once selected all inputs, outputs, command sources
and setpoints will be automatically configured by the
soft
ware.
For further information see the section that details the
precise settings for each macro. Please see installation
section of this manual.
16.
Set the Minim
um Speed at which the attached motor
should run.
Converter with control units CU240D-2
72 Operating Instructions, 04/2015, FW V4.7.3, A5E34262100B AB