Eight sources in total are available for speed setpoint. You can select one of them with the
combination of digital input signals SPD1, SPD2 and SPD3:
External analog speed setpoint (analog input 1)
Fixed speed setpoint 1 (p1001)
Fixed speed setpoint 2 (p1002)
Fixed speed setpoint 3 (p1003)
Fixed speed setpoint 4 (p1004)
1 0 1 Fixed speed setpoint 5 (p1005)
Fixed speed setpoint 6 (p1006)
Fixed speed setpoint 7 (p1007)
The ramp-function generator is used to limit acceleration in the event of abrupt setpoint
changes and thus helps prevent load surges during drive operation.
The ramp-up time p1120 and ramp-down time p1121 can be used to set acceleration and
deceleration ramps separately. This allows a smoothed transition in the event of setpoint
changes.