● Speed loop PI/P switching
Five switching modes in total are available for PI/P switching:
– using torque setpoint
– using an external digital input signal (G-CHANGE)
– using speed setpoint
– using acceleration setpoint
– using pulse deviation
If you select either of the PI/P switching modes (except the second mode), you need to
set the conditional threshold as shown in the above screenshot.
Note
PI/P switching
This function is not
available in
mode and responds with a delay of several
Low frequency vibration suppression
Low frequency vibration suppression is a position setpoint filter function. It can suppress the
vibration frequency within 0.5 Hz to 62.5 Hz.
This function is only available in IPos and EPOS control modes.
To use the vibration suppression function, you need to configure the following parameters
accordingly:
p29035 0 to 1 0 - Vibration suppression activation
= 0: disable
p31581 0 to 1 0 - Vibration suppression filter type
= 0: rugged
Vibration suppression filter frequency
Vibration suppression filter damping