EasyManua.ls Logo

Siemens siprotec 7SA522 - Page 111

Siemens siprotec 7SA522
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.3 Power swing detection (optional)
111
7SA522 Manual
C53000-G1176-C155-3
bility. For release of the power swing detection a further criterion is therefore used. In
2-39 the range for steady state instability is shown. This range is detected in the dis-
tance protection relay. This is done by calculating the center of the ellipse and check-
ing if the actual measured X value is less than this value.
Figure 2-39 Steady state instability range
Trajectory
Symmetry
In addition to these measures, a comparison of the three phases is done to ensure that
they are symmetrical. During a power swing condition in the single pole open condi-
tion, only two of the three phases will have an impedance trajectory. In this case only
these 2 remaining phase trajectories are checked to ensure that they are symmetrical.
Power Swing
Detection
To ensure stable and secure operation of the power swing detection without risking un-
wanted power swing blocking during power system faults, a logical combination of a
number of measuring criteria are used.
Figure 2-40 Logic diagram of power swing detection

Table of Contents

Other manuals for Siemens siprotec 7SA522

Related product manuals