2 Functions
84
7SA522 Manual
C53000-G1176-C155-3
Figure 2-21 Directional characteristic with quadrature or memorized voltages
Determination of
Direction in Case of
Series-compensa-
ted Lines
The directional characteristics and their displacement by the source impedance apply
also for lines with series capacitors. If a short-circuit occurs behind the local series ca-
pacitors, the short-circuit voltage however reverses its direction until the protective
spark gap has picked up (see Figure 2-22).
Figure 2-22 Voltage characteristic while a fault occurs after a series capacitor.
a) without pickup of the protective spark gap PSG
b) with pickup of the protective spark gap PSG
The distance protection function would thus detect a wrong fault direction. The use of
memorised voltages however ensures that the direction is correctly detected (see
Figure 2-23a).
Since the voltage prior to the fault is used for determining the direction, the zeniths of
the directional characteristics in dependence of the source impedance and infeed con-
ditions before the fault are thus far displaced that the capacitor reactance — which is

Table of Contents

Other manuals for Siemens siprotec 7SA522

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA522 and is the answer not in the manual?

Siemens siprotec 7SA522 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA522
CategoryProtection Device
LanguageEnglish

Related product manuals