3 - 6
Siemens AG January 1999
   
Table 3.6 Line differential protection
  Current threshold I
1
(release with local current)
I/I
N line
Differential current I/I
N line
Delay time T
0.00 to 1.50 (step 0.01)
0.05 to 2.50 (step 0.01)
0.00 to 60.00 s (step 0.01 s)
 
Stabilization with 2nd harmonic I
2fN
/I
fN
Resetting ratio
see Figure 3.1
10 to 80 %
approx. 0.7 @ pick-up value (I
stab
=0)
All current values refer to symmetrical current with standard connection.
  Pick-up time for two-sided infeed
with 4 x setting value
Reset time
approx. 20 to 28 ms without stabilization by
2 harm
approx. 32 to 42 ms with stabilization by
2 harm
approx. 35 ms
 with pre-settings
under reference conditions
Local current threshold
Differential current
"3 % of set value, min 0.02 @ I
N
"5 % of set value, min 0.02 @ I
N
  Auxiliary supply voltage in range
0.8
v U
H
/U
HN
v@1.15
Temperature in range 0 _C
v
amb
v 40 _C
Frequency in range 0.9
v f/f
N
v 1.1
v1%
v1 %/10K
v4%
  Number
Asymmetry of pilot wire pair at 800 Hz
Maximum loop resistance
Permissible induced longitudinal voltages
for direct connection with pilot wire
for connection via isolating transformer
2
preferably symmetrical telephone wire pairs
with 73 /km loop resistance and 60 nF/km
capacitance
max. 10
-3
1200
v1.2 kV, but max. 60 % of the test voltage of
the pilot wires
w1.2 kV, but max. 60 % of the test voltage of
the pilot wires and max. 60 % of the test volĆ
tage of the isolating transformer
   
  (order option)
Monitoring signal
Delay of fail signal
Operating time of transfer tripping
Prologation of transfer trip signal
2000 Hz, pulse code modulation
1 to 60 s (step 1 s)
approx. 65 ms
0.00 to 5.00 s (step 0.01 s)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Siprotec 7SD600 and is the answer not in the manual?

Siemens Siprotec 7SD600 Specifications

General IconGeneral
BrandSiemens
ModelSiprotec 7SD600
CategoryProtection Device
LanguageEnglish

Related product manuals