Table 3.7 Remote tripping
Tripping of the remote line end only available for devices with pilot wire monitoring
  Prolongation time for transmission to remote
station
Delay time of the received signal from remote
station
Prolongation time of the received signal from
remote station
0.00 to 60.00 s (step 0.01 s)
0.00 to 60.00 s (step 0.01 s)
0.00 to 60.00 s (step 0.01 s)
 Delay time/reset delay time 1%or10ms
  Transmission time without delay approx. 80 ms
  
Table 3.8 Lockout function
   for differential protection and remote tripping until resetting
 via binary input and/or local operation
  
Table 3.9 Additional functions
   Operating currents
Measuring range
1
;
2
;
diff
;
stab
0 to 240 %
N
gg
Tolerance (
1
)
N
3 % of nominal value or of
measured value
   Storage of last 8 faults
  Resolution for operational events
fault events
Max. time deviation
1s
1ms
0.01 %
   
max. 8 faults
Storage time (from start or trip command)
Max. length per recording T
max
Pre-fault time T
pre
Post-fault time T
post
Sampling rate at 50 Hz
Sampling rate at 60 Hz
Max. of overall 5 s, pre and post
fault settable
0.30 to 5,00 s (step 0.01 s)
0.05 to 0.50 s (step 0.01 s)
0.05 to 0.50 s (step 0.01 s)
1 instantaneous value per ms
1 instantaneous value per 0.83 ms
  by test tripping