EasyManua.ls Logo

Siemens SIPROTEC 7SK80 - Page 158

Siemens SIPROTEC 7SK80
490 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
2.10 Monitoring Functions
SIPROTEC, 7SK80, Manual
E50417-G1140-C344-A4, Release date 08.2010
158
Figure 2-46 Logic Diagram of the fast current sum monitoring
Note
If the current input IN is configured as a sensitive transformer or if the connection mode A,G2,C,G; G->B or
A,G2,C,G; G2->B was set for the current transformers at parameter 251 CT Connect., current sum mon-
itoring is not possible.
AD Transformer Monitoring
The digitized sampled values are being monitored in respect of their plausibility. If the result is not plausible,
message 181 „Error A/D-conv.“ is issued. The protection is blocked, thus preventing unwanted operation.
Furthermore, a fault record is generated for recording of the internal fault.

Table of Contents

Related product manuals