EasyManuals Logo
Home>Siemens>Protection Device>SIPROTEC 7UT613 series

Siemens SIPROTEC 7UT613 series User Manual

Siemens SIPROTEC 7UT613 series
638 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #126 background imageLoading...
Page #126 background image
2 Functions
126
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-43 Busbar protection with connection via summation current transformers (SCT)
Different schemes are possible for the connection of the current transformers. The
same CT connection method must be used for all feeders of a busbar.
The scheme as illustrated in figure 2-44 is the most commonly used. The three input
windings of the summation transformer are connected to the CT currents I
L1
, I
L3
and
I
E
. This connection is suitable for all kinds of systems regardless of the conditioning of
the system neutral. It is characterised by an increased sensitivity for earth faults.
Figure 2-44 Summation Transformer Connection L1-L3-E
For a symmetrical three-phase current (where the earth residual component I
E
= 0)
the single-phase summation current is W = √3 times the winding unit value, as shown
in figure 2-45, i.e. the summation flux (ampere turns) is the same as it would be for
single-phase current √3 times the value flowing through the winding with the least
number of turns (ratio 1). For three-phase symmetrical fault currents equal to rated
current 1 x I
N
, the secondary single-phase current is I
M
= 100 mA. All relay character-
istic operating values are based on this type of fault and this current.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7UT613 series and is the answer not in the manual?

Siemens SIPROTEC 7UT613 series Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7UT613 series
CategoryProtection Device
LanguageEnglish

Related product manuals